Weil Mclain oil fired burner (Carlin) from 2008.
- One zone system (does NOT have a domestic hot water coil)
- Pressure high causing relief valve to open at 30 PSI
- Replaced: Pressure Relief Valve, Water feeder (Watts 12-15 PSI), and Extrol 30 Expansion Tank Today in hopes of correcting issue
-Verified Circulator has 120V and operates.
- Pressure reaches 30 PSI at approximately 140 degrees which causes relief valve to relieve
Where should I go from here?